installation site popping pressure
steam manifold of boiler or superheater outlet rated steam pressure is less than 5.9MPa control safety valve 1.04 times of working pressure
working safety valve 1.06 times of working pressure
rated steam pressure is larger than 5.9MPa control safety valve 1.05 times of working pressure
working safety valve 1.08 times of working pressure
direct-current boiler superheater outlet control safety valve 1.08 times of working pressure
working safety valve 1.1 times of working pressure
reheater   1.1 times of working pressure
Start Separator   1.1 times of working pressure