Safety Valve Series

Product drawing»

Structural drawing»

You are here: News > News Detail

Safety Valve Sizing

2012-03-30

Safety valves must always be sized and able to vent any source of steam so that the pressure within the protected apparatus cannot exceed the maximum allowable accumulated pressure (MAAP). This not only means that the valve has to be positioned correctly, but that it is also correctly set. The safety valve must then also be sized correctly, enabling it to pass the required amount of steam at the required pressure under all possible fault conditions.

Once the type of safety Valves has been established, along with its set pressure and its position in the system, it is necessary to calculate the required discharge capacity of the valve. Once this is known, the required orifice area and nominal size can be determined using the manufacturer's specifications.

In order to establish the maximum capacity required, the potential flow through all the relevant branches, upstream of the valve, need to be considered.

In applications where there is more than one possible flow path, the sizing of the safety valve becomes more complicated, as there may be a number of alternative methods of determining its size. Where more than one potential flow path exists, the following alternatives should be considered:

  • The safety valve can be sized on the maximum flow experienced in the flow path with the greatest amount of flow.
  • The safety valve can be sized to discharge the flow from the combined flow paths.

This choice is determined by the risk of two or more devices failing simultaneously. If there is the slightest chance that this may occur, the valve must be sized to allow the combined flows of the failed devices to be discharged. However, where the risk is negligible, cost advantages may dictate that the valve should only be sized on the highest fault flow. The choice of method ultimately lies with the company responsible for insuring the plant.

For example, consider the pressure vessel and automatic pump-trap (APT) system as shown in Figure 9.4.1. The unlikely situation is that both the APT and pressure reducing valve (PRV 'A') could fail simultaneously. The discharge capacity of safety valve 'A' would either be the fault load of the largest PRV, or alternatively, the combined fault load of both the APT and PRV 'A'.

This document recommends that where multiple flow paths exist, any relevant safety valve should, at all times, be sized on the possibility that relevant upstream pressure control valves may fail simultaneously.

 

Related Products of Safety

Safety Relief Valves

SAFETY VALVES

Safety Valves

YIHUAN Safety valves

TIANFA Safety valves

Shanghai MeiYan Yi Pump & Valve Co., Ltd.
MeiYan Yi safety valve Contact MeiYan Yi
Shanghai Enine Pump & Valve Co., Ltd.
Enine safety valve Contact Enine
Shanghai Saitai Pump & Valve CO., Lid.
Saitai safety valve Contact Saitai
Shanghai Fengqi Industrial Development Co., Ltd.
FengQi safety valve Contact FengQi