Safety Valve Installation
Safety Valves Installation
Seat tightness
Seat tightness is an important consideration when selecting and installing a
safety valve, as not only can it lead to a continuous loss of system fluid, but
leakage can also cause deterioration of the sealing faces, which can lead to
premature lifting of the valve.
The seat tightness is affected by three
main factors; firstly by the characteristics of the safety valve, secondly by
the installation of the safety valve and thirdly, by the operation of Safety Relief Valves.
Characteristics of the safety valve
For a metal-seated Safety Relief Valves to provide an acceptable shut-off, the sealing
surfaces need to have a high degree of flatness with a very good surface finish.
The disc must articulate on the stem and the stem guide must not cause any undue
frictional effects. Typical figures required for an acceptable shut-off for a
metal seated valve are 0.5 mm for surface finish and two optical light bands for
flatness. In addition, for a reasonable service life, the mating and sealing
surfaces must have a high wear resistance.
Unlike ordinary isolation
valves, the net closing force acting on the disc is relatively small, due to
there being only a small difference between the system pressure acting on the
disc and the spring force opposing it.
Resilient or elastomer seals
incorporated into the valve discs are often used to improve shut-off, where
system conditions permit. It should be noted, however, that a soft seal is often
more susceptible to damage than a metal seat.
Safety valve installation
Seat damage can often occur when a valve is first lifted as part of the
general plant commissioning procedure, because very often, dirt and debris are
present in the system. To ensure that foreign matter does not pass through the
valve, the system should be flushed out before the safety valve is installed and
the valve must be mounted where dirt, scale and debris cannot collect.
It
is also important on steam applications to reduce the propensity for leakage by
installing the valve so that condensate cannot collect on the upstream side of
the disc. This can be achieved by installing the safety valve above the steam
pipe as shown in Figure 9.5.1.
Where safety valves are installed below the pipe, steam will condense, fill the pipe and wet the upstream side of the safety valve seat. This type of installation is not recommended but is shown in Figure 9.5.2 for reference purposes.
Also, it is essential at all times to ensure that the downstream pipework is well drained so that downstream flooding (which can also encourage corrosion and leakage) cannot occur, as shown in Figure 9.5.3.
Operation of the safety valve
Leakage can also be experienced when there is dirt or scale sitting on the
seating face. This usually occurs during the periodic lifting demanded by
insurance companies and routine maintenance programs. Further lifting of the
lever will generally clear any dirt that may be on the seating face.
The
vast majority of safety valve seat leakage problems occur after initial
manufacture and test. These problems typically result from damage during
transit, and sometimes as a result of misuse and contamination, or because of
poor installation.
Most safety valve standards do not include detailed
shut-off parameters. For those that do, the requirements and recommended test
procedures are usually based on the API 527 standard, which is commonly used
throughout the safety valve industry.
The procedure for testing valves
that have been set on air involves blocking all secondary leakage paths, whilst
maintaining the valve at 90% of the set pressure on air (see Figure 9.5.4). The
outlet of the safety valve is connected to a 6 mm internal diameter pipe, the
end of which is held 12.7 mm below the surface of water contained in a suitable,
transparent vessel. The number of bubbles discharged from this tube per minute
is measured. For the majority of valves set below 70 bar g, the acceptance
criteria is 20 bubbles per minute.
For valves set on steam or water, the leakage rate should be assessed using
the corresponding setting media. For steam, there must be no visible leakage
observed against a black background for one minute after a three-minute
stabilisation period. In the case of water, there is a small leakage allowance,
dependent on the orifice area, of 10 ml per hour per inch of the nominal inlet
diameter.
The above procedure can be time consuming, so it is quite
common for manufacturers to employ a test using alternative methods, for
example, using accurate flow measuring equipment that is calibrated against the
parameters set in API 527.
Under no circumstances should any
additional load be applied to the easing lever nor should the valve be gagged in
order to increase the seat tightness. This will affect the operating
characteristics and can result in the safety valve failing to lift in
overpressure conditions. If there is an unacceptable level of seat leakage, the
valve can be refurbished or repaired, but only by authorised personnel, working
with the approval of the manufacturer, and using information supplied by the
manufacturer.
Commonly supplied spare parts typically include springs,
discs and nozzles, resilient seals and gaskets. Many valves have seat rings
which are not removable and these can sometimes be re-profiled and re-lapped in
the body. However, it is important that the size of seat orifice is maintained
exactly in line with the original drawings since this can alter the effective
area and, subsequently affect the set pressure.
It is unacceptable for
the disc to be lapped directly onto the seat in the body, since a groove will be
created on the disc preventing a consistent shut-off after lifting.
In
the case of resilient seal valves usually the seal (which is normally an 'O'
ring or disc) can be changed in the disc assembly.
If Independent
Authority Approval is to be maintained then it is mandatory that the repairer is
acting as the manufacturer's approved agent. For ASME approved valves, the
repairer must be independently approved by the National Board and is
subsequently allowed to apply a 'VR' stamp, which indicates a valve has been
repaired.
Marking
Safety valve standards are normally very specific about the information which must be carried on the valve. Marking is mandatory on both the shell, usually cast or stamped, and the name-plate, which must be securely attached to the valve. A general summary of the information required is listed below:
On the shell
- Size designation.
- Material designation of the shell.
- Manufacturer's name or trademark.
- Direction of flow arrow.
On the identification plate:
- Set pressure (in bar g for European valves and psi g for ASME valves).
- Number of the relevant standard (or relevant ASME stamp).
- Manufacturer's model type reference.
- Derated coefficient of discharge or certified capacity.
- Flow area.
- Lift and overpressure.
- Date of manufacture or reference number.
National Board approved ASME stamps are applied as follows:
V | ASME I approved safety relief valves. |
UV | ASME VIII approved safety relief valves. |
UD | ASME VIII approved rupture disc devices. |
NV | ASME III approved pressure relief valves. |
VR | Authorised repairer of pressure relief valves. |
Table 9.5.1 details the marking system required by T?V and Table 9.5.2 details the fluid reference letters.
The Kdr or aW value can vary according to the relevant fluid and is either suffixed or prefixed by the identification letter shown in Table 9.5.2.
Installation
Safety valves are precision items of safety equipment; they are set to close
tolerances and have accurately machined internal parts. They are susceptible to
misalignment and damage if mishandled or incorrectly installed.
Valves
should be transported upright if possible and they should never be carried or
lifted by the easing lever. In addition, the protective plugs and flange
protectors should not be removed until actual installation. Care should also be
taken during movement of the valve to avoid subjecting it to excessive shock as
this can result in considerable internal damage or misalignment.
Inlet pipework
When designing the inlet pipework, one of the main considerations is to ensure that the pressure drop in this pipework is minimised. EN ISO 4126 recommends that the pressure drop be kept below 3% of the set pressure when discharging. Where safety valves are connected using short 'stub' connections, inlet pipework must be at least the same size as the safety valve inlet connection. For larger lines or any line incorporating bends or elbows, the branch connection should be at least two pipe sizes larger than the safety valve inlet connection, at which point it is reduced in size to the safety valve inlet size (see Figure 9.5.5a). Excessive pressure loss can lead to 'chatter', which may result in reduced capacity and damage to the seating faces and other parts of the valve. In order to reduce the pressure loss in the inlet, the following methods can be adopted:
- Increase the diameter of the pipe. (see Figure 9.5.5 (a)).
- Ensure that any corners are suitably rounded. The EN ISO 4126 standard recommends that corners should have a radius of not less than one quarter of the bore (see Figure 9.5.5 (b)).
- Reduce the inlet pipe length.
- Install the valve at least 8 to 10 pipe diameters downstream from any converging or diverging 'Y' fitting, or any bend (see Figure 9.5.5 (c)).
- Never install the safety valve branch directly opposite a branch on the lower side of the steam line.
- Avoid take-off branches (such as for other processes) in the inlet piping, as this will increase the pressure drop.
Safety valves should always be installed with the bonnet vertically upwards.
Installing the valve in any other orientation can affect the performance
characteristics.
The API Recommended Practice 520 guidelines also state
that the safety valve should not be installed at the end of a long horizontal
pipe that does not normally have flow through it. This can lead to the
accumulation of foreign material or condensate in the pipe, which may cause
unnecessary damage to the valve, or interfere with its operation.
Outlet pipework
There are two possible types of discharge system - open and closed systems.
Open system discharge directly into the atmosphere whereas closed systems
discharge into a manifold along with other safety valves.
It is
recommended that discharge pipework for steam and gas systems should rise,
whereas for liquids, it should fall. However, it is important to drain any
rising discharge pipework.
Horizontal pipework should have a downward
gradient of at least 1 in 100 away from the valve; this gradient ensures that
the discharge pipe is self-draining. However, any vertical rises will still
require separate drainage. Note that any drainage systems form part of the
overall discharge system and are therefore subject to the same precautions that
apply to the discharge systems, notably that they must not affect the valve
performance, and any fluid must be discharged to a safe location.
It is
essential to ensure that fluid cannot collect on the downstream side of a safety
valve, as this will impair the performance of the valve and cause corrosion of
the spring and internal parts. Many safety valves are provided with a body drain
connection, if this is not used or not provided, then a small bore drain should
be fitted in close proximity to the valve outlet (see Figure 9.5.3).
One
of the main concerns in closed systems is the pressure drop or built-up
backpressure in the discharge system. As mentioned in Tutorial 9.2, this can
drastically affect the performance of a safety valve. The EN ISO 4126 standard
states that the pressure drop should be maintained below 10% of the set
pressure. In order to achieve this, the discharge pipe can be sized using
Equation 9.5.1.
Where:
d | = | Pipe diameter (mm) |
Le | = | Equivalent length of pipe (m) |
= | Discharge capacity (kg / h) | |
P | = | Safety valve set pressure (bar g) x Required percentage pressure drop |
vg | = | Specific volume of saturated steam at the pressure (P) (m / kg) |
The pressure (P) should be taken as the maximum allowable pressure drop
according to the relevant standard. In the case of EN ISO 4126, this would be
10% of the set pressure and it is at this pressure vg is
taken.
Example 9.5.1
Calculate the necessary diameter of the discharge pipework for a safety valve
designed to discharge 1 000 kg / h of saturated steam, given that the steam is
to be discharged into a vented tank via the pipework, which has an equivalent
length of 25 m. The set pressure of the safety valve is 10 bar g and the
acceptable backpressure is 10% of the set pressure. (Assume there is no pressure
drop along the tank vent).
Answer: If the maximum 10% backpressure
is allowed, then the gauge pressure at the Safety Relief Valves outlet will be:
Using saturated steam tables, the corresponding specific volume at this
pressure is, vg = 0.88 m? / kg.
Applying Equation 9.5.1:
Therefore, the pipework connected to the outlet of the safety valve should
have an internal diameter of at least 54 mm. With schedule 40 pipe, this would
require a DN65 pipe.
If it is not possible to reduce the backpressure to
below 10% of the set pressure, a balanced safety valve should be
used.
Balanced safety valves require that their bonnets be vented to
atmosphere. In the case of the balanced bellows type, there will be no discharge
of the process fluid, so they can be vented directly to the atmosphere. The main
design consideration is to ensure that this vent will not become blocked, for
example, by foreign material or ice. With the balanced piston type,
consideration must be given to the fact that process fluid may be discharged
through the bonnet vent. If discharging to a pressurised system, the vent has to
be suitably sized, so that no backpressure exists above the
piston.
Safety valves that are installed outside of a building for
discharge directly into the atmosphere should be covered using a hood. The hood
allows the discharge of the fluid, but prevents the build up of dirt and other
debris in the discharge pipework, which could affect the backpressure. The hood
should also be designed so that it too does not affect the backpressure.
Manifolds
Manifolds must be sized so that in the worst case (i.e. when all the manifold valves are discharging), the pipework is large enough to cope without generating unacceptable levels of backpressure. The volume of the manifold should ideally be increased as each valve outlet enters it, and these connections should enter the manifold at an angle of no greater than 45